406.13 Single-Pole Separable-Connector Type.

According to 406.14(D), the use of single-pole separable connectors shall be performed by a qualified person.
Click to Enlarge
According to 406.14(D), the use of single-pole separable connectors shall be performed by a qualified person.

Code Change Summary: New code section provides requirements for single-pole separable connectors.

NEC Article 406 is all about receptacles, cord connectors, and attachment plugs yet it has never provided any installation requirements for single-pole separable connectors which are very common, especially on stage sets or with temporary events.

In the 2020 NEC®, section 406.13 was added to address single-pole separable connectors. Language from Article 520 for theaters, motion picture, television studios, and similar locations was used when creating the new requirements in 406.13.

UL 1691 Single Pole Locking-Type Separable Connectors contains the criteria for the construction, performance, and marking requirements to certify single-pole separable connectors.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

This code section did not exist.

2020 Code Language:

N 406.13 Single-Pole Separable-Connector Type. Single-pole separable connectors shall be listed and labeled and shall comply with 406.13(A) through (D).

N 406.13(A) Locking or Latching Type. Single-pole separable connectors shall be of either the locking or latching type and marked with the manufacturer’s name or identification and voltage and ampere ratings.

N 406.13(B) Identification. Connectors designated for connection to the grounded circuit conductor shall be identified by a white-colored housing; connectors designated for connection to the grounding circuit conductor shall be identified by a green-colored housing.

Did You Like This? Let Us Know With A Like! Thanks!

406.13 Single-Pole Separable-Connector Type.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image of the single-pole separable connectors:

Which of the following is true?

A: The yellow colored connector housing is designated for connection to the grounding circuit conductor.
B: The green colored connector housing is designated for connection to the grounding circuit conductor.
C: The green colored connector housing is designated as the grounded circuit conductor.
D: Green colored connector housings are not permitted.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.