NFPA 731, Section 5.1.6 is all about the proper function of entry and exit delay features in a security system to reduce the likelihood of false alarms. Annex A, Section A.5.1.6.2 in the back of NFPA 731 states the following:
“A.5.1.6.2 The mechanism, such as a keypad or other human/ machine interface (HMI), is to be located no farther than a normal 15-second walk from the point of entry. Depending on the size of the premises, the mechanism can be opposite the point of entry, in the next room, or even the same room. This provision is in this standard so that compliance with ANSI/SIA CP-01, Control Panel Standard — Features for False Alarm Reduction, can be achieved”.
Below is a sample of NFPA 731. For the complete section, see the actual NFPA 731 text at NFPA.ORG. Once there, click on the free access link to the latest edition of NFPA 731.
5.1.6 Entry/Exit Delay.
5.1.6.1 A delay circuit that allows entry into protected premises shall be limited to only those initiating devices, such as door contacts installed on entry doors and interior sensors that must be bypassed to allow access to the mechanism that is used to place the system in a disarmed state.
5.1.6.2 The mechanism that is used to disarm the system shall be reachable within 15 seconds of the entry portal.
5.1.6.3 The entry time shall not exceed 240 seconds.
5.1.6.4 The exit delay shall be in compliance with ANSI/SIA CP-01, Control Panel Standard — Features for False Alarm Reduction, Section 4.2.2.
5.1.6.5 The entry delay shall be in compliance with ANSI/SIA CP-01, Control Panel Standard — Features for False Alarm Reduction, Section 4.2.3.
Which of the following is true?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |