NEC Article 250 Grounding.

Equipment grounding must be done in accordance with the National Electrical Code (NEC).
Click to Enlarge
Equipment grounding must be done in accordance with the National Electrical Code (NEC).

NFPA 731 Section 4.8 requires grounding to be done in accordance with the National Electrical Code or NEC® (NFPA 70).

The NEC® covers grounding in Article 250. Typically, in a security system installation, an electrician provides a branch circuit for the security system installer and the security contractor takes it from there to supply the security system control panel. Sometimes the electrician is also licensed to install the security system. Either way, ensuring that the security system is properly grounded is a job shared by both types of installers.

The code language below provides general NEC® rules for fixed in place equipment grounding that apply to many security system installations:

Below is a sample of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the latest NEC® edition of NFPA 70.

NEC 250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods. Exposed, normally non–current carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized shall be connected to an equipment grounding conductor under any of the following conditions:

(1) Where within 2.5 m (8 ft) vertically or 1.5 m (5 ft) horizontally of ground or grounded metal objects and subject to contact by persons

(2) Where located in a wet or damp location and not isolated

(3) Where in electrical contact with metal

(4) Where in a hazardous (classified) location as covered by Articles 500 through 517

(5) Where supplied by a wiring method that provides an equipment grounding conductor, except as permitted by 250.86, Exception No. 2, for short sections of metal enclosures

(6) Where equipment operates with any terminal at over 150 volts to ground

Exception No. 1: If exempted by special permission, the metal frame of electrically heated appliances that have the frame permanently and effectively insulated from ground shall not be required to be grounded.

Exception No. 2: Distribution apparatus, such as transformer and capacitor cases, mounted on wooden poles at a height exceeding 2.5 m (8 ft) above ground or grade level shall not be required to be grounded.

Exception No. 3: Listed equipment protected by a system of double insulation, or its equivalent, shall not be required to be connected to the equipment grounding conductor. Where such a system is employed, the equipment shall be distinctively marked.

Did You Like This? Let Us Know With A Like! Thanks!

NEC Article 250 Grounding.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for fixed in place equipment supplied by a wiring method that provides an equipment grounding conductor?

A: Grounding is not permitted.
B: It must be isolated if equipment operates with any terminal at over 150 volts to ground.
C: Grounding of the alarm system is done in accordance with NFPA 730.
D: The exposed, normally non–current carrying metal parts of the fixed equipment shall be connected to an equipment grounding conductor.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.