338.10(B)(4). Insert an informational note as follows:
Informational Note: This section includes service entrance cables with a round configuration commonly known as SER cable. The interior installation of this cable is governed by the same rules as apply to nonmetallic sheathed cable.
338.10(B)(4)(a)(3). Revise to read as follows:
Where installed in thermal insulation, the ampacity shall be in accordance with the 60°C (140°F) conductor temperature rating. The maximum conductor temperature rating shall be permitted to be used for ampacity adjustment and correction purposes, if the final derated ampacity does not exceed that for a 60°C (140°F) rated conductor.
Click here to see the Massachusetts amendments to the 2023 NEC®.
Which of the following is true regarding SE cable as amended in Massachusetts?