210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.

In MA, this receptacle requires GFCI protection since it is located within a cabinet supporting a sink.
Click to Enlarge
In MA, this receptacle requires GFCI protection since it is located within a cabinet supporting a sink.

MA amendments.

210.8. Insert the following exception after the first paragraph:

Exception: Permanently connected equipment and cord-and-plug connected stationary equipment that is listed, but incompatible with GFCI protective devices as made available by the manufacturer of the circuit protection currently installed, shall be permitted to omit such protection provided it is installed and inspected in accordance with the provisions of Rule11 of this Code. This exception shall expire on January 1, 2026.

Revise the second paragraph to read as follows:

For the purposes of this section, when determining distance from receptacles the distance shall be measured as the shortest path the supply cord of equipment connected to the receptacle would follow without piercing a floor, wall, ceiling, fixed barrier, or without passing through a cabinet door opening, doorway, or window.

210.8(A)(8). Revise to read as follows:

(8) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink, or where located within a cabinet supporting a sink.

210.8(B)(7). Revise to read as follows:

(7) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink, or where located within a cabinet supporting a sink.

210.8(F). Delete this requirement.

Click here to see the Massachusetts amendments to the 2023 NEC®.

Did You Like This? Let Us Know With A Like! Thanks!

210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true regarding GFCI protection for a 125-volt, single phase, 15 or 20-amp receptacle as amended in Massachusetts?

A: GFCI protection is required for a receptacle located within a cabinet supporting a sink.
B: All outdoor outlets for dwellings that are supplied by single-phase branch circuits rated 150 volts to ground or less, 50 amperes or less, shall have ground-fault circuit-interrupter protection for personnel.
C: GFCI protection is required for a receptacle installed 7 feet from the top inside edge of the bowl of the sink.
D: GFCI protection is required for a receptacle installed 6 feet from the outer most edge of the bowl of the sink.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.