250.122(F) Size of Equipment Grounding Conductors. Conductors in Parallel.

All equipment grounding conductors in the gutter must be joined together.
Click to Enlarge
All equipment grounding conductors in the gutter must be joined together.

Code Change Summary: Clarifications were made regarding equipment grounding conductors installed in parallel.

Several rules must be followed when installing conductors in parallel. The majority of the rules for parallel conductors are found in 310.10(H) and additional rules pertaining to installing equipment grounding conductors in parallel are located in 250.122(F).

In the 2017 NEC®, the rules for parallel equipment grounding conductors in multiconductor cables are now separate from individual parallel equipment grounding conductor installations in raceways or cable trays. As well, auxiliary gutters are now mentioned in this section.

If a sheet metal auxiliary gutter is installed and supplied by multiconductor cables in parallel, the gutter is required to be connected to the equipment grounding conductors in each parallel cable. These equipment grounding conductors must be sized from Table 250.122 based on the size of the overcurrent device protecting the multiconductor cables.

Provisions were made to allow a single equipment grounding conductor, sized in accordance with 250.122, in combination with the equipment grounding conductors provided within the multiconductor cables. This new allowance recognizes that situations can occur where the equipment grounding conductor in each parallel multiconductor cable may not be sufficient in size for larger feeders or branch circuits in the same auxiliary gutter. In this case, an individual equipment grounding conductor is permitted to be installed in addition to the equipment grounding conductors provided within the multiconductor cables as long as all equipment grounding conductors are connected together.

Below is a preview of Article 250. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

(F) Conductors in Parallel. Where conductors are installed in parallel in multiple raceways or cables as permitted in 310.10(H), the equipment grounding conductors, where used, shall be installed in parallel in each raceway or cable. Where conductors are installed in parallel in the same raceway, cable, or cable tray as permitted in 310.10(H), a single equipment grounding conductor shall be permitted. Equipment grounding conductors installed in cable tray shall meet the minimum requirements of 392.10(B)(1)(c). Each equipment grounding conductor shall be sized in compliance with 250.122.

2017 Code Language:

(F) Conductors in Parallel. For circuits of parallel conductors as permitted in 310.10(H), the equipment grounding conductor shall be installed in accordance with (1) or (2).

N (1) Conductor Installations in Raceways, Auxiliary Gutters, or Cable Trays.

(a) Single Raceway or Cable Tray. If conductors are installed in parallel in the same raceway or cable tray, a single wire-type conductor shall be permitted as the equipment grounding conductor. The wire-type equipment grounding conductor shall be sized in accordance with 250.122, based on the overcurrent protective device for the feeder or branch circuit. Wire-type equipment grounding conductors installed in cable trays shall meet the minimum requirements of 392.10(B)(1)(c). Metal raceways or auxiliary gutters in accordance with 250.118 or cable trays complying with 392.60(B) shall be permitted as the equipment grounding conductor.

(b) Multiple Raceways. If conductors are installed in parallel in multiple raceways, wire-type equipment grounding conductors, where used, shall be installed in parallel in each raceway. The equipment grounding conductor installed in each raceway shall be sized in compliance with 250.122 based on the overcurrent protective device for the feeder or branch circuit. Metal raceways or auxiliary gutters in accordance with 250.118 or cable trays complying with 392.60(B) shall be permitted as the equipment grounding conductor.

N (2) Multiconductor Cables.

(a) If multiconductor cables are installed in parallel, the equipment grounding conductor(s) in each cable shall be connected in parallel.

(b) If multiconductor cables are installed in parallel in the same raceway, auxiliary gutter, or cable tray, a single equipment grounding conductor that is sized in accordance with 250.122 shall be permitted in combination with the equipment grounding conductors provided within the multiconductor cables and shall all be connected together.

(c) Equipment grounding conductors installed in cable trays shall meet the minimum requirements of 392.10(B)(1)(c). Cable trays complying with 392.60(B), metal raceways in accordance with 250.118, or auxiliary gutters shall be permitted as the equipment grounding conductor.

(d) Except as provided in 250.122(F)(2)(b) for raceway or cable tray installations, the equipment grounding conductor in each multiconductor cable shall be sized in accordance with 250.122 based on the overcurrent protective device for the feeder or branch circuit.

Did You Like This? Let Us Know With A Like! Thanks!

250.122(F) Size of Equipment Grounding Conductors. Conductors in Parallel.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when installing multiconductor cables in parallel to supply a sheet metal auxiliary gutter?

A: The equipment grounding conductor in each multiconductor cable shall be sized in accordance with NEC Table 250.66.
B: A single equipment grounding conductor that is sized in accordance with 250.122 shall be permitted in combination with the equipment grounding conductors provided within the multiconductor cables and shall all be connected together.
C: Equipment grounding conductors in multiconductor cables are NOT permitted to be installed in parallel.
D: Equipment grounding conductors are NOT permitted to be installed in parallel.