Section 250.52(B) describes the following items and materials that cannot be used as a grounding electrode:
Item 3 above makes it clear that the steel rebar of a pool cannot be used as an actual grounding electrode.
Even though NEC® section 680.26(B) requires the pool steel to be bonded to all other conductive components mentioned in 680.26(B)(1) through (7), it is still not permitted to be used as an actual grounding electrode.
The bonding in 680.26 is there to place everything in the pool area on the same potential which helps to eliminate voltage gradients in the area or stray voltages that can be dangerous for swimmers.
A grounding electrode system serves a different purpose altogether. One of which is to limit the voltage imposed by lightning. Using the pool steel as the grounding electrode could jeopardize swimmers who really shouldn’t be swimming during a lightning storm anyways.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.
2023 Code Language:
250.52(B) Not Permitted for Use as Grounding Electrodes. The following systems and materials shall not be used as grounding electrodes:
(1) Metal underground gas piping systems
(2) Aluminum
(3) The structures and structural rebar described in 680.26(B)(1) and (B)(2)
Which of the following items can be used as a grounding electrode?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |