Article 100. Bonding Jumper, Supply-Side.

The supply-side bonding jumper ensures the required electrical conductivity between metal parts required to be electrically connected.
Click to Enlarge
The supply-side bonding jumper ensures the required electrical conductivity between metal parts required to be electrically connected.

A supply-side bonding jumper (SSBJ) is a conductor installed on the supply side of a service or within service equipment enclosures, or for a separately derived system, that ensures the required electrical conductivity between metal parts required to be electrically connected. Unfortunately, the definition does not describe what can be used as a SSBJ.

At present, the only code section providing any possible clarity on what constitutes a SSBJ is highlighted in yellow below. This section only pertains to a SSBJ used in a separately derived system:

250.30(A)(2) Supply-Side Bonding Jumper. If the source of a separately derived system and the first disconnecting means are located in separate enclosures, a supply-side bonding jumper shall be installed with the circuit conductors from the source enclosure to the first disconnecting means enclosure. A supply-side bonding jumper shall not be required to be larger than the derived ungrounded conductors. The supply-side bonding jumper shall be permitted to be of nonflexible metal raceway type or of the wire or bus type as follows:

(1) A supply-side bonding jumper of the wire type shall comply with 250.102(C), based on the size of the derived ungrounded conductors.

(2) A supply-side bonding jumper of the bus type shall have a cross-sectional area not smaller than a supply-side bonding jumper of the wire type as determined in 250.102(C).

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2023 Code Language:

Article 100.

Bonding Jumper, Supply-Side. (Supply-Side Bonding Jumper). A conductor installed on the supply side of a service or within a service equipment enclosure(s), or for a separately derived system, that ensures the required electrical conductivity between metal parts required to be electrically connected.

Did You Like This? Let Us Know With A Like! Thanks!

Article 100. Bonding Jumper, Supply-Side.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following ensures the required electrical conductivity between metal parts required to be electrically connected on the supply side of a service?

A: The equipment grounding conductor.
B: The supply-side bonding jumper.
C: The main bonding jumper.
D: The system bonding jumper.
Please register or sign in for electrical continuing education courses.