690.31(C)(2) Cable Tray.

Be sure the rules used apply to the correct cable tray type.
Click to Enlarge
Be sure the rules used apply to the correct cable tray type.

Code Change Summary: New requirements added for cable tray installations.

In the 2023 NEC®, language was added in Article 690 to provide additional details for single-conductor PV wire smaller than 1/0 AWG installed in cable trays.

Section 690.31(C)(2) has allowed the use of PV or distributed generation (DG) cable in cable trays for PV installations but until this code change, there really hasn’t been any direction given on adjustment factors or the layering of these smaller conductors in the cable tray.

Article 392 provides additional information but not for cables smaller than 1/0 AWG.

In the 2023 NEC®, the language in 690.31(C)(2) was expanded with the following additional code language that requires a careful read:

Where installed in uncovered cable trays, ampacity of single-conductor PV wire smaller than 1/0 AWG, the adjustment factors for 1/0 AWG single conductor cable in 392.80(A)(2) shall be permitted to be used.

Where single-conductor PV wire smaller than 1/0 AWG is installed in ladder or ventilated trough cable trays, the following shall apply:

(1) All single conductors shall be installed in a single layer.

(2) Conductors that are bound together to comprise each circuit pair shall be permitted to be installed in other than a single layer.

(3) The sum of diameters of all single conductor cables shall not exceed the cable tray width.

The final language for the code change omitted the word “or” but the public input behind the new language specifically addressed “ladder or ventilated trough cable trays”. Wire mesh cable trays are often used in rooftop PV cable installations, and it is likely that this new code language will be expanded to include other cable tray types not currently mentioned in the 2023 code language.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

690.31(C)(2) Cable Tray. Single-conductor PV wire or cable of all sizes or distributed generation (DG) cable of all sizes, with or without a cable tray rating, shall be permitted in cable trays installed in outdoor locations, provided that the cables are supported at intervals not to exceed 12 inches and secured at intervals not to exceed 4-1/2 feet.

2023 Code Language:

690.31(C)(2) Cable Tray. Single-conductor PV wire or cable of all sizes or distributed generation (DG) cable of all sizes, with or without a cable tray rating, shall be permitted in cable trays installed in outdoor locations, provided that the cables are supported at intervals not to exceed 12 inches and secured at intervals not to exceed 54 inches.

Where installed in uncovered cable trays, ampacity of single-conductor PV wire smaller than 1/0 AWG, the adjustment factors for 1/0 AWG single conductor cable in 392.80(A)(2) shall be permitted to be used.

Where single-conductor PV wire smaller than 1/0 AWG is installed in ladder ventilated trough cable trays, the following shall apply:

(1) All single conductors shall be installed in a single layer.

(2) Conductors that are bound together to comprise each circuit pair shall be permitted to be installed in other than a single layer.

(3) The sum of diameters of all single conductor cables shall not exceed the cable tray width.

Did You Like This? Let Us Know With A Like! Thanks!

690.31(C)(2) Cable Tray.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

According to the 2023 language in 690.31(C)(2), which of the following is true for single-conductor PV wire smaller than 1/0 AWG installed in ladder ventilated trough cable trays?

A: They must be installed in a raceway within the cable tray.
B: Conductors shall NOT be bound together to comprise each circuit pair.
C: Single conductors shall be bundled tightly.
D: All single conductors shall be installed in a single layer.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.