Code Change Summary: A new code section requires surge protection for certain occupancies supplied by a feeder.
The 2020 NEC® introduced a new requirement in Section 230.67 to have a Type 1 or Type 2 surge protective device (SPD) for dwelling unit services. Additionally, an SPD is required when an existing service is replaced.
In the 2023 NEC®, surge protection is now required in Section 215.18 for the specific dwelling types listed below that are supplied by a feeder:
The same code language was also added in Section 225.42 which covers outside branch circuits and feeders.
Apartment complexes, hotels, motels, and nursing homes are typically supplied by an electrical service that in turn supplies (through a feeder) other dwelling units or sleeping units. Often, each dwelling unit panelboard is a significant distance from the electrical service. Requiring surge protection for feeder supplied dwelling type units ensures that the SPD is closer to the load where the sensitive electronics need the protection.
A surge is a transient wave of voltage or current. The duration is not consistent but is usually less than a few milliseconds. Transients and Surges can have peak values in excess of 10kA or 10kV. During a surge, the waveform has a very rapid rise to the peak and then falls off at a much slower rate. Transients and Surges can be caused by external sources such as lightning or short circuits, or from internal sources such as variable speed drives, contactor or capacitor switching.
A surge protective device protects the sensitive electronics in most modern appliances as well as devices installed for the safety of the occupants such as AFCI, GFCI and smoke/carbon monoxide detection, and other equipment commonly found in dwellings.
SPD’s are most effective when they are closest to the branch circuits being protected. Simply having surge protection at the electrical service will not afford the same protection as having a SPD at the dwelling unit panelboard supplied by the load end of a long run of feeder conductors. This is why the requirement for surge protection at the service equipment from Section 230.67(B) has an exception to permit the SPD to be located at each next level distribution equipment downstream toward the load instead of at the service.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.
2020 Code Language:
This code section did not exist.
2023 Code Language:
N 215.18 Surge Protection.
(A) Surge-Protective Device. Where a feeder supplies any of the following, a surge-protective device (SPD) shall be installed:
(1) Dwelling units
(2) Dormitory units
(3) Guest rooms and guest suites of hotels and motels
(4) Areas of nursing homes and limited-care facilities used exclusively as patient sleeping rooms
(B) Location. The SPD shall be installed in or adjacent to distribution equipment, connected to the load side of the feeder, that contains branch circuit overcurrent protective device(s) that supply the locations specified in 215.18(A).
(C) Type. The SPD shall be a Type 1 or Type 2 SPD.
(D) Replacement. Where the distribution equipment supplied by the feeder is replaced, all of the requirements of this section shall apply.
(E) Ratings. SPDs shall have a nominal discharge current rating (In) of not less than 10kA.
Which of the following is true from Section 215.18?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |