OESC 334.15(C) In Unfinished Basements.

In Oregon, the code language placing restrictions on the size and method of running nonmetallic sheathed cables in a crawl space or unfinished basement has been amended and only applies to NM cables installed in an unfinished basement.
Click to Enlarge
In Oregon, the code language placing restrictions on the size and method of running nonmetallic sheathed cables in a crawl space or unfinished basement has been amended and only applies to NM cables installed in an unfinished basement.

A simple strike through of the phrase “and crawl spaces” makes it clear that in Oregon, the rules in NEC® 334.15(C) only apply to unfinished basements:

334.15(C) In Unfinished Basements and Crawl Spaces. Where cable is run at angles with joists in unfinished basements and crawl spaces, it shall be permissible to secure cables not smaller than two 6 AWG or three 8 AWG conductors directly to the lower edge of the joists. Smaller cables shall be run either through bored holes in joists or on running boards. Nonmetallic-sheathed cable installed on the wall of an unfinished basement shall be permitted to be installed in a listed conduit or tubing or shall be protected in accordance with 300.4.

Oregon amendments to the 2023 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: 2023 OESC

  Click here to view the OESC  

Did You Like This? Let Us Know With A Like! Thanks!

OESC 334.15(C) In Unfinished Basements.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when installing 12 AWG nonmetallic sheathed cable (type NM) in a crawl space?

A: The NM cable cannot be installed directly on the edge of a joist.
B: The NM cable must only be installed through bored holes in the joists.
C: The OESC has amended the crawl space restrictions out of the NEC for NM cable.
D: Any NM cable installed in a crawl space must be NMC (corrosive resistant).